10.2 General Technical Data
Protection and Features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips if the temperature
reaches 203 °F ± 10 °F[95 °C ±5 °C]. An overload temperature cannot be reset until the temperature of the
heatsink is below 158 °F ± 10 °F [70 °C ± 5 °C] (Guideline - these temperatures may vary for different power sizes,
enclosures etc.). VLT
®
AQUA Drive has an auto derating function to avoid its heatsink reaching 203 °F [95 °C].
The frequency converter is protected against short circuits on motor terminals U, V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
Line power supply (L1, L2, L3)
Supply voltage 200–240 V ±10%
Supply voltage 380–480 V ±10%
Supply voltage 525–600 V ±10%
Supply voltage 525–690 V ±10%
AC line voltage low/line drop-out:
During low AC line voltage or a line drop-out, the adjustable frequency drive continues until the intermediate circuit voltage
drops below the minimum stop level, which corresponds typically to 15% below the adjustable frequency drive's lowest rated
supply voltage. Power-up and full torque cannot be expected at AC line voltage lower than 10% below the adjustable frequency
drive's lowest rated supply voltage.
Supply frequency 50/60 Hz +4/-6%
The adjustable frequency drive power supply is tested in accordance with IEC61000-4-28, 50 Hz +4/-6%.
Max. temporary imbalance between line phases 3.0% of rated supply voltage
True Power Factor (λ) 0.9 nominal at rated load
Displacement Power Factor (cosφ) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) enclosure type A maximum 2 times/min.
Switching on input supply L1, L2, L3 (power-ups) enclosure type B, C maximum 1 time/min.
Switching on input supply L1, L2, L3 (power-ups) enclosure type D, E, F maximum 1 time/2 min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/480/600/690
V maximum.
Motor output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–590 Hz
*
Switching on output Unlimited
Ramp times 1–3600 s
*
Dependent on power size.
Torque characteristics
Starting torque (Constant torque) maximum 110% for 1 min.
*
Starting torque maximum 135% up to 0.5 s
*
Overload torque (Constant torque) maximum 110% for 1 min.
*
*Percentage relates to VLT AQUA Drive's nominal torque.
Specifications
VLT
®
AQUA Drive
Instruction Manual
10-12 MG20M922 - VLT
®
is a registered Danfoss trademark
10
10

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals