10 Specifications
10.1 Power-dependent Specifications
10.1.1 Line Power Supply 1 x 200–240 V AC
Line Power Supply 1 x 200–240 V AC - Normal overload 110% for 1 minute
Adjustable frequency drive
Typical Shaft Output [kW]
P1K1
1.1
P1K5
1.5
P2K2
2.2
P3K0
3.0
P3K7
3.7
P5K5
5.5
P7K5
7.5
P15K
15
P22K
22
Typical Shaft Output [HP] at 240 V 1.5 2.0 2.9 4.0 4.9 7.5 10 20 30
IP20/Chassis A3 - - - - - - - -
IP21/NEMA 1 - B1 B1 B1 B1 B1 B2 C1 C2
IP55/NEMA 12 A5 B1 B1 B1 B1 B1 B2 C1 C2
IP66 A5 B1 B1 B1 B1 B1 B2 C1 C2
Output current
Continuous (3 x 200–240 V) [A] 6.6 7.5 10.6 12.5 16.7 24.2 30.8 59.4 88
Intermittent(3 x 200–240 V) [A] 7.3 8.3 11.7 13.8 18.4 26.6 33.4 65.3 96.8
Continuous kVA (208 V AC) [kVA] 5.00 6.40 12.27 18.30
Max. input current
Continuous (1 x 200–240 V) [A] 12.5 15 20.5 24 32 46 59 111 172
Intermittent (1 x 200–240 V) [A] 13.8 16.5 22.6 26.4 35.2 50.6 64.9 122.1 189.2
Max. pre-fuses
1)
[A]
20 30 40 40 60 80 100 150 200
Additional specifications
Estimated power loss at rated
max. load [W]
4)
44 30 44 60 74 110 150 300 440
Max. cable size (line power, motor,
brake)
[mm
2
]/(AWG)
2)
[0.2–4]/(4–10) [10]/(7) [35]/(2) [50]/(1)/0 [95]/(4/0)
Weight enclosure IP20 (lb [kg]) 10.8 [4.9] - - - - - - - -
Weight enclosure IP21 (lb [kg])
-
50.71
[23]
50.71
[23]
50.71
[23]
50.71 [23]
50.71
[23]
59.53 [27]
99.21
[45]
143.3
[65]
Weight enclosure IP55 (lb [kg])
-
50.71
[23]
50.71
[23]
50.71
[23]
50.71 [23]
50.71
[23]
59.53 [27]
99.21
[45]
143.3
[65]
Weight enclosure IP66 (lb [kg])
-
50.71
[23]
50.71
[23]
50.71
[23]
50.71 [23]
50.71
[23]
59.53 [27]
99.21
[45]
143.3
[65]
Efficiency
3)
0.968 0.98 0.98 0.98 0.98 0.98 0.98 0.98 0.98
Table 10.1 Line Power Supply 1 x 200–240 V AC - Normal Overload 110% for 1 Minute
Specifications
VLT
®
AQUA Drive
Instruction Manual
MG20M922 - VLT
®
is a registered Danfoss trademark 10-1
10
10