10.4 Connection Tightening Torques
Power (hp [kW]) Torque (Nm)
Enclo-
sure
200–240 V 380–480/500 V 525–600 V 525–690 V Line power Motor
DC
connection
Brake Ground Relay
A2
0.34–3
[0.25–2.2]
0.5–5 [0.37–4.0] 1.8 1.8 1.8 1.8 3 0.6
A3 4–5 [3.0–3.7] 7.5–10 [5.5–7.5]
1–10 [0.75–
7.5]
1.5–10 [1.1–
7.5]
1.8 1.8 1.8 1.8 3 0.6
A4
0.34–3
[0.25–2.2]
0.5–5 [0.37–4.0] 1.8 1.8 1.8 1.8 3 0.6
A5
0.34–5
[0.25–3.7]
0.5–10 [0.37–7.5]
1–10 [0.75–
7.5]
1.8 1.8 1.8 1.8 3 0.6
B1
7.5–10 [5.5–
7.5]
15–20 [11–15]
15–20 [11–
15]
1.8 1.8 1.5 1.5 3 0.6
B2 15 [11]
25 [18]
30 [22]
25 [18]
30 [22]
15 [11]
30 [22]
4.5
4.5
4.5
4.5
3.7
3.7
3.7
3.7
3
3
0.6
0.6
B3
7.5–10 [5.5–
7.5]
15–20 [11–15]
15–20 [11–
15]
1.8 1.8 1.8 1.8 3 0.6
B4
15–20 [11–
15]
25–40 [18–30]
25–40 [18–
30]
4.5 4.5 4.5 4.5 3 0.6
C1
20–30 [15–
22]
40–60 [30–45]
40–60 [30–
45]
10 10 10 10 3 0.6
C2
40–50 [30–
37]
75–100 [55–75]
75–100 [55–
75]
40–100 [30–
75]
14/24
1)
14/24
1)
14 14 3 0.6
C3
25–30 [18–
22]
50–60 [37–45]
50–60 [37–
45]
60–75 [45–
55]
10 10 10 10 3 0.6
C4
40–50 [30–
37]
75–100 [55–75]
75–100 [55–
75]
14/24
1)
14/24
1)
14 14 3 0.6
Table 10.27 Tightening of Terminals
1)
For different cable dimensions x/y, where x ≤ 95 mm
2
and y ≥ 95 mm
2
.
Specifications
VLT
®
AQUA Drive
Instruction Manual
MG20M922 - VLT
®
is a registered Danfoss trademark 10-27
10
10