Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
0 - 10V
+
-
130BB678.10
Function Setting
6-10 Terminal 53
Low Voltage
0.07 V*
6-11 Terminal 53
High Voltage
10 V*
6-14 Terminal 53
Low Ref./Feedb.
Value
0*
6-15 Terminal 53
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
Table 6.4 Analog Speed Reference (Voltage)
NOTE!
Note switch setting for selecting voltage or current.
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
A53
U - I
4 - 20mA
+
-
130BB679.10
Function Setting
6-12 Terminal 53
Low Current
4 mA*
6-13 Terminal 53
High Current
20 mA*
6-14 Terminal 53
Low Ref./Feedb.
Value
0*
6-15 Terminal 53
High Ref./Feedb.
Value
50*
* = Default Value
Notes/comments:
Table 6.5 Analog Speed Reference (Current)
NOTE!
Note switch setting for selecting voltage or current.
Parameters
FC
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
37
50
53
54
55
42
39
130BB680.10
Function Setting
5-10 Terminal 18
Digital Input
[8] Start*
5-12 Terminal 27
Digital Input
[7] External
Interlock
* = Default Value
Notes/comments:
Table 6.6 Run/Stop Command with External Interlock
Application Set-up Examples
VLT
®
AQUA Drive
Instruction Manual
6-2 MG20M922 - VLT
®
is a registered Danfoss trademark
66