5.3.14 Switches S201, S202, and S801
Switches S201 (A53) and S202 (A54) are used to select a current (0–20
mA) or a voltage (0–10 V) configuration of the analog input terminals 53
and 54 respectively.
Switch S801 (BUS TER.) can be used to enable termination on the RS-485
port (terminals 68 and 69).
See drawing
Diagram showing all electrical terminals
in section
Electrical
Installation.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF
NOTE!
It is recommended to only change switch position at power off.
VLT
®
AQUA Drive Design Guide 5 How to Install