7.5 Examples
7.5.1 Writing a parameter value
Change par. 4-14
Motor Speed High Limit [Hz]
to 100 Hz.
Write the data in EEPROM.
PKE = E19E Hex - Write single word in par. 4-14
Motor Speed High Limit
[Hz]
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 03E8 Hex - Data value 1000, corresponding to 100 Hz, see
Conversion.
The message will look like this:
Note: par. 4-14
Motor Speed High Limit [Hz]
is a single word, and the
parameter command for write in EEPROM is “E”. Parameter number 4-14
is 19E in hexadecimal.
The response from the slave to the master will be:
7.5.2 Reading a parameter value
Read the value in par. 3-41
Ramp 1 Ramp Up Time
PKE = 1155 Hex - Read parameter value in par. 3-41
Ramp 1 Ramp Up
Time
IND = 0000 Hex
PWEHIGH = 0000 Hex
PWELOW = 0000 Hex
If the value in par. 3-41
Ramp 1 Ramp Up Time
is 10 s, the response from
the slave to the master will be:
NOTE!
3E8 Hex corresponds to 1000 decimal. The conversion index for par. 3-41
Ramp 1 Ramp Up Time
is -2, i.e., 0.01.
Par. 3-41 is of the type
Unsigned 32
.
7 RS-485 Installation and Set-up VLT
®
AQUA Drive Design Guide
7-12
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
7

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals