EasyManuals Logo

Danfoss vlt aqua Design Guide

Danfoss vlt aqua
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #189 background imageLoading...
Page #189 background image
7.1.4 VLT AQUA Parameter Settings for Modbus Communication
The following parameters apply to the RS-485 interface (FC-port):
Parameter Number Parameter name Function
8-30 Protocol Select the application protocol to run on the RS-485 interface
8-31 Address Set the node address. Note: The address range depends on the protocol se-
lected in par. 8-30
8-32 Baud Rate Set the baud rate. Note: The default baud rate depends on the protocol se-
lected in par. 8-30
8-33 PC port parity/Stop bits Set the parity and number of stop bits. Note: The default selection depends
on the protocol selected in par. 8-30
8-35 Min. response delay Specify a minimum delay time between receiving a request and transmitting
a response. This can be used for overcoming modem turnaround delays.
8-36 Max. response delay Specify a maximum delay time between transmitting a request and receiving
a response.
8-37 Max. inter-char delay Specify a maximum delay time between two received bytes to ensure timeout
if transmission is interrupted.
7.1.5 EMC Precautions
The following EMC precautions are recommended in order to achieve interference-free operation of the RS-485 network.
NOTE!
Relevant national and local regulations, for example, regarding protective ground connection, must be observed. The RS-485 com-
munication cable must be kept away from motor and brake resistor cables to avoid coupling of high frequency noise from one cable
to another. Normally a distance of 200 mm (8 inches) is sufficient, but keeping the greatest possible distance between the cables is
generally recommended, especially where cables run in parallel over long distances. When crossing is unavoidable, the RS-485 cable
must cross motor and brake resistor cables at an angle of 90 degrees.
VLT
®
AQUA Drive Design Guide 7 RS-485 Installation and Set-up
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
7-3
7

Table of Contents

Other manuals for Danfoss vlt aqua

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss vlt aqua and is the answer not in the manual?

Danfoss vlt aqua Specifications

General IconGeneral
Supply Voltage200-240V, 380-500V, 525-600V
EnclosureIP20
FeaturesEnergy optimization
ApprovalsCE, UL, cUL
Input Voltage Range200-240V, 380-500V, 525-600V
Output Voltage Range0 to supply voltage
Protection FeaturesOvervoltage, Undervoltage, Overcurrent, Short circuit, Ground fault
Communication InterfacesPROFIBUS
Cooling MethodAir-cooled

Related product manuals