7.11.3 Bus Speed Reference Value
Speed reference value is transmitted to the adjustable frequency drive in
a relative value expressed as %. The value is transmitted in the form of
a 16-bit word; in integers (0-32767) the value 16384 (4000 Hex) corre-
sponds to 100%. Negative figures are formatted by means of 2’s com-
plement. The Actual Output frequency (MAV) is scaled in the same way
as the bus reference.
The reference and MAV are scaled as follows:
7 RS-485 Installation and Set-up VLT
®
AQUA Drive Design Guide
7-30
MG.20.N5.22 - VLT
®
is a registered Danfoss trademark
7