1-20 Motor Power [kW]
Range: Function:
Application
dependent*
[Application dependant]
1-22 Motor Voltage
Range: Function:
Application
dependent*
[Application dependant]
1-23 Motor Frequency
Range: Function:
Application
dependent*
[20 - 1000 Hz] Select the motor frequency value from the motor nameplate data.For 87 Hz operation with 230/400
V motors, set the nameplate data for 230 V/50 Hz. Adapt par. 4-13
Motor Speed High Limit
[RPM]
and par. 3-03
Maximum Reference
to the 87 Hz application.
NOTE!
This parameter cannot be adjusted while the motor is running.
1-24 Motor Current
Range: Function:
Application
dependent*
[Application dependant]
NOTE!
This parameter cannot be adjusted while the motor is running.
1-25 Motor Nominal Speed
Range: Function:
Application
dependent*
[100 - 60000 RPM]
NOTE!
This parameter cannot be changed while the motor is running.
VLT AQUA High Power Instruction Manual
5 How to program the adjustable frequency
drive
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
5-15