13-10 Comparator Operand
Array [6]
Option: Function:
[183] Drive stopped
[183] Drive stopped A stop command
(Jog, Stop, Qstop, Coast) is issued and
not from the SLC itself.
[185] Drive in hand
mode
[185] Drive in hand mode High when the
frequency converter is in hand mode.
[186] Drive in auto
mode
[186] Drive in auto mode High when the
frequency converter is in auto mode.
[187] Start command
given
[190] Digital input x30
2
[191] Digital input x30
3
[192] Digital input x30
4
[193] Digital input x46
1
[194] Digital input x46
2
[195] Digital input x46
3
[196] Digital input x46
4
[197] Digital input x46
5
[198] Digital input x46
6
[199] Digital input x46
7
13-11 Comparator Operator
Array [6]
Option: Function:
Select the operator to be used in the
comparison. This is an array parameter
containing comparator operators 0 to 5.
[0] <
Select [0] < for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand is smaller than the
fixed value in 13-12 Comparator Value. The
result will be FALSE, if the variable selected in
13-10 Comparator Operand is greater than the
fixed value in 13-12 Comparator Value.
[1] * (equal)
Select [1] for the result of the evaluation to
be TRUE, when the variable selected in
13-10 Comparator Operand is approximately
equal to the fixed value in 13-12 Comparator
Value.
[2] >
Select [2] > for the inverse logic of option <
[0].
13-11 Comparator Operator
Array [6]
Option: Function:
[5] TRUE longer
than..
[6] FALSE
longer
than..
[7] TRUE
shorter
than..
[8] FALSE
shorter
than..
13-12 Comparator Value
Array [6]
Range: Function:
Size related* [-100000.000 -
100000.000 ]
Enter the ‘trigger level’ for the
variable that is monitored by
this comtor. This is an array
parameter containing comtor
values 0 to 5.
3.14.4 13-1* RS Flip Flops
The Reset-Set Flip Flops hold the signal until set/reset.
Par. 13-15
RS-FF Operand S
Par. 13-16
RS-FF Operand R
130BB959.10
Illustration 3.51
Two parameters are used and the output can be used in
the logic rules and as events.
R
S
Flip Flop Output
130BB960.10
Illustration 3.52
The two operators can be selected from a long list. As a
special case, the same digital input can be used as both
Set and Reset, making it possible to use the same digital
input as start/stop. The following settings can be used to
set up the same digital input as start/stop (example given
with DI32 but is not a requirement).
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 119
3
3