13-02 Stop Event
Select the boolean (TRUE or FALSE) input to activate Smart Logic
Control.
Option: Function:
[90] ATEX ETR cur. warning
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91] ATEX ETR cur. alarm
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92] ATEX ETR freq. warning
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21] ]. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93] ATEX ETR freq. alarm
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94] RS Flipflop 0
[95] RS Flipflop 1
[96] RS Flipflop 2
[97] RS Flipflop 3
[98] RS Flipflop 4
[99] RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-03 Reset SLC
Option: Function:
[0] * Do not reset
SLC
Retains programmed settings in all
parameter group 13 parameters (13-**).
[1] Reset SLC Resets all parameter group 13 parameters
(13-**) to default settings.
3.14.3 13-1* Comparators
Comparators are used for comparing continuous variables
(i.e. output frequency, output current, analog input etc.) to
fixed preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
130BB672.10
Illustration 3.50
In addition, there are digital values that will be compared
to fixed time values. See explanation in 13-10 Comparator
Operand. Comparators are evaluated once in each scan
interval. Use the result (TRUE or FALSE) directly. All
parameters in this parameter group are array parameters
with index 0 to 5. Select index 0 to programme
Comparator 0, select index 1 to programme Comparator 1,
and so on.
13-10 Comparator Operand
Array [6]
Option: Function:
Choice [1] to [31] are variables which
will be compared based on their values.
Choice [50] to [186] are digital values
(TRUE/FALSE) where the comparison is
based on the amount of time during
which they are set to TRUE or FALSE,
respectively. See 13-11 Comparator
Operator.
Select the variable to be monitored by
the comparator.
[0] * DISABLED
[0] DISABLED The comparator is disabled.
[1] Reference
[1] Reference The resulting remote
reference (not local) as a percentage.
[2] Feedback
[2] Feedback In the unit [RPM] or [Hz]
[3] Motor speed
[3] Motor speed [RPM] or [Hz]
[4] Motor current
[4] Motor current [A]
[5] Motor torque
[5] Motor torque [Nm]
[6] Motor power
[6] Motor power [kW] or [hp]
[7] Motor voltage
[7] Motor voltage [V]
[8] DC-link voltage
[8] DC-link voltage [V]
[9] Motor thermal
[9] Motor thermal Expressed as a
percentage.
[10] Drive thermal
[10] VLT thermal Expressed as a
percentage.
[11] Heat sink temp.
[11] Heat sink temp Expressed as a
percentage.
[12] Analog input
AI53
[12] Analog input AI53 Expressed as a
percentage.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
116 MG33ME02 - VLT
®
is a registered Danfoss trademark
3