Parameter Setting Notes
13-00 SL Controller Mode On
13-01 Start Event TRUE
13-02 Stop Event FALSE
13-40 Logic Rule Boolean 1 [0]
[37] Digital
Input DI32
13-42 Logic Rule Boolean 2 [0] [2] Running
13-41 Logic Rule Operator 1
[0]
[3] AND
NOT
13-40 Logic Rule Boolean 1 [1]
[37] Digital
Input DI32
13-42 Logic Rule Boolean 2 [1] [2] Running
13-41 Logic Rule Operator 1
[1]
[1] AND
13-15 RS-FF Operand S [0]
[26]
Logicrule 0
Output from 13-41
[0]
13-16 RS-FF Operand R [0]
[27]
Logicrule 1
Output from 13-41
[1]
13-51 SL Controller Event [0]
[94] RS
Flipflop 0
Output from
evaluating 13-15
and 13-16
13-52 SL Controller Action [0] [22] Run
13-51 SL Controller Event [1]
[27]
Logicrule 1
13-52 SL Controller Action [1] [24] Stop
Table 3.22
13-15 RS-FF Operand S
Option: Function:
[0] False
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current limit
[7] Out of current range
[8] Below I low
[9] Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
13-15 RS-FF Operand S
Option: Function:
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
[29] Logic rule 3
[30] SL Time-out 0
[31] SL Time-out 1
[32] SL Time-out 2
[33] Digital input DI18
[34] Digital input DI19
[35] Digital input DI27
[36] Digital input DI29
[37] Digital input DI32
[38] Digital input DI33
[39] Start command
[40] Drive stopped
[41] Reset Trip
[42] Auto-reset Trip
[43] Ok key
[44] Reset key
[45] Left key
[46] Right key
[47] Up key
[48] Down key
[50] Comparator 4
[51] Comparator 5
[60] Logic rule 4
[61] Logic rule 5
[70] SL Time-out 3
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[75] Start command given
[76] Digital input x30/2
[77] Digital input x30/3
[78] Digital input x30/4
[79] Digital input x46/1
[80] Digital input x46/3
[81] Digital input x46/5
[82] Digital input x46/7
[83] Digital input x46/9
[84] Digital input x46/11
[85] Digital input x46/13
[90] ATEX ETR cur. warning
[91] ATEX ETR cur. alarm
[92] ATEX ETR freq. warning
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
120 MG33ME02 - VLT
®
is a registered Danfoss trademark
3