Q1 My Personal Menu
Q2 Quick Setup
Q4 Smart Setup
Q5 Changes Made
0RPM 0.00A 1(1)
Quick Menus
Illustration 2.13
Select Quick setup to go through a limited amount of
parameters to get the motor running almost optimally. The
default setting for the other parameters considers the
desired control functions and the configuration of signal
inputs/outputs (control terminals).
The selection of parameter is effected by means of the
arrow keys. The parameters in the following table are
accessible.
Parameter Setting
0-01 Language
1-20 Motor Power [kW]
[kW]
1-22 Motor Voltage
[V]
1-23 Motor Frequency
[Hz]
1-24 Motor Current
[A]
1-25 Motor Nominal Speed
[rpm]
5-12 Terminal 27 Digital Input
[0] No function*
1-29 Automatic Motor Adaptation (AMA)
[1] Enable complete
AMA
3-02 Minimum Reference
[rpm]
3-03 Maximum Reference
[rpm]
3-41 Ramp 1 Ramp up Time
[sec]
3-42 Ramp 1 Ramp Down Time
[sec]
3-13 Reference Site
Table 2.2
* If terminal 27 is set to “no function”, no connection to
+24 V on terminal 27 is necessary.
Select Changes made to get information about:
•
the last 10 changes. Use the [
▲
] [
▼
] navigation
keys to scroll between the last 10 changed
parameters.
•
the changes made since default setting.
Select Loggings to get information about the display line
read-outs. The information is shown as graphs.
Only display parameters selected in 0-20 Display Line 1.1
Small and 0-24 Display Line 3 Large can be viewed. It is
possible to store up to 120 samples in the memory for
later reference.
How to Programme
VLT
®
AutomationDrive Programmming Guide
16 MG33ME02 - VLT
®
is a registered Danfoss trademark
22