2.1.7 Initial Commissioning
The easiest way of carrying out the initial commissioning is
by using the [Quick Menu] key and follow the quick set-up
procedure using LCP 102 (read table from left to right).
The example applies to open loop applications.
Press
Quick
Menu
Q2 Quick Menu
OK
0-01 Language
OK
Set language
1-20 Motor Power [kW]
OK
Set Motor nameplate power
1-22 Motor Voltage
OK
Set Nameplate voltage
1-23 Motor Frequency
OK
Set Nameplate frequency
1-24 Motor Current
OK
Set Nameplate current
1-25 Motor Nominal Speed
OK
Set Nameplate speed in RPM
5-12 Terminal 27 Digital Input
OK
If terminal default is Coast
inverse it is possible to change
this setting to No function. No
connection to terminal 27 is
then needed for running AMA
1-29 Automatic Motor Adaptation
(AMA)
OK
Set desired AMA function.
Enable complete AMA is
recommended
3-02 Minimum Reference
OK
Set the minimum speed of the
motor shaft
3-03 Maximum Reference
OK
Set the maximum speed of the
motor shaft
3-41 Ramp 1 Ramp up Time
OK
Set the ramping up time with
reference to synchronous
motor speed, n
s
3-42 Ramp 1 Ramp Down Time
OK
Set the ramping down time
with reference to synchronous
motor speed, n
s
3-13 Reference Site
OK
Set the site from where the
reference must work
Table 2.3
Another easy way of commissioning the drive is by using
the Smart Application Setup (SAS), which can also be
found under the Quick Menu. Follow the indications on
the successive screens for setting-up the applications
listed.
How to Programme
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 17