3-13 Reference Site
Option: Function:
Select which reference site to activate.
[0] * Linked to
Hand / Auto
Use local reference when in Hand mode; or
remote reference when in Auto mode.
[1] Remote Use remote reference in both Hand mode
and Auto mode.
[2] Local Use local reference in both Hand mode and
Auto mode.
NOTE
When set to [2] Local, the frequency
converter will start with this setting
again following a 'power down'.
3-14 Preset Relative Reference
Range: Function:
0.00
%*
[-100.00 -
100.00 %]
The actual reference, X, is increased or
decreased with the percentage Y, set in
3-14 Preset Relative Reference. This results
in the actual reference Z. Actual reference
(X) is the sum of the inputs selected in
3-15 Reference 1 Source, 3-16 Reference 2
Source, 3-17 Reference 3 Source and
8-02 Control Source.
Relative
Z=X+X*Y/100
Resulting
actual
reference
Y
X
130BA059.12
Z
Illustration 3.22
X
100
%
0-100
Z
Y
X+X*Y/100
P 3-14
130BA278.10
Illustration 3.23
3-15 Reference Resource 1
Option: Function:
Select the reference input to be used
for the first reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up to
three different reference signals. The
3-15 Reference Resource 1
Option: Function:
sum of these reference signals
defines the actual reference.
[0] No function
[1] * Analog input 53
[2] Analog input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] Digital pot.meter
[21] Analog input X30-11 (General Purpose I/O Option Module)
[22] Analog input X30-12 (General Purpose I/O Option Module)
[29] Analog Input X48/2
3-16 Reference Resource 2
Option: Function:
Select the reference input to be
used for the second reference
signal. 3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
[0] No function
[1] Analog input 53
[2] Analog input 54
[7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] * Digital pot.meter
[21] Analog input X30-11
[22] Analog input X30-12
[29] Analog Input X48/2
3-17 Reference Resource 3
Option: Function:
Select the reference input to be
used for the third reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
[0] No function
[1] Analog input 53
[2] Analog input 54
[7] Frequency input 29
[8] Frequency input 33
[11] * Local bus reference
[20] Digital pot.meter
[21] Analog input X30-11
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
58 MG33ME02 - VLT
®
is a registered Danfoss trademark
3