0-38 Display Text 2
Range: Function:
0 * [0 - 0 ] Enter a text which can be viewed in the graphical
display by selecting Display Text 2 [38] in
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2
Small, 0-22 Display Line 1.3 Small, 0-23 Display Line 2
Large or 0-24 Display Line 3 Large.
0-39 Display Text 3
Range: Function:
0 * [0 - 0 ] Enter a text which can be viewed in the graphical
display by selecting Display Text 3 [39] in
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2
Small, 0-22 Display Line 1.3 Small, 0-23 Display Line 2
Large or 0-24 Display Line 3 Large.
3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on
the LCP.
0-40 [Hand on] Key on LCP
Option: Function:
[0] * Disabled No effect when [Hand On] is pressed. Select
[0] Disabled to avoid accidental start of the
frequency converter in Hand on mode.
[1] * Enabled
The LCP switches to Hand on mode directly
when [Hand on] is pressed.
[2] Password After pressing [Hand on] a password is
required. If 0-40 [Hand on] Key on LCP is in
included in My Personal Menu, define the
password in 0-65 Quick Menu Password.
Otherwise define the password in 0-60 Main
Menu Password.
[3] Hand Off/On When [Hand On] is pressed once, the LCP
switches to Off mode. When pressed again,
the LCP switches to Hand on mode.
[4] Hand Off/On
w. Passw.
Same as [3] but a password is required (see
[2]).
0-41 [Off] Key on LCP
Option: Function:
[0] * Disabled Avoids accidental stop of the frequency
converter.
[1] * Enabled
[2] Password
Avoids unauthorised stop. If 0-41 [Off] Key on LCP
is included in the Quick Menu, then define the
password in 0-65 Quick Menu Password.
0-42 [Auto on] Key on LCP
Option: Function:
[0] * Disabled Avoid accidental start of the frequency converter
in Auto mode.
0-42 [Auto on] Key on LCP
Option: Function:
[1] * Enabled
[2] Password
Avoids unauthorised start in Auto mode. If
0-42 [Auto on] Key on LCP is included in the
Quick Menu, then define the password in
0-65 Quick Menu Password.
0-43 [Reset] Key on LCP
Option: Function:
[0] * Disabled No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1] * Enabled
[2] Password
Avoids unauthorised resetting. If
0-43 [Reset] Key on LCP is included in the
Quick Menu, then define the password in
0-65 Quick Menu Password.
[7] Enabled
without OFF
Resets the frequency converter without
setting it in Off mode.
[8] Password
without OFF
Resets the frequency converter without
setting it in Off mode. A password is
required when pressing [Reset] (see [2]).
3.2.6 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option: Function:
[0] * No copy
[1] All to LCP Copies all parameters in all set-ups
from the frequency converter memory
to the LCP memory.
[2] All from LCP Copies all parameters in all set-ups
from the LCP memory to the
frequency converter memory.
[3] Size indep. from
LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to
programme several frequency
converters with the same function
without disturbing motor data.
[4] File from MCO to
LCP
[5] File from LCP to
MCO
[6] Data from DYN to
LCP
[7] Data from LCP to
DYN
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
32 MG33ME02 - VLT
®
is a registered Danfoss trademark
3
3