NOTE
This parameter cannot be adjusted while the motor is
running.
0-51 Set-up Copy
Option: Function:
[0] * No copy No function
[1] Copy to set-
up 1
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 1.
[2] Copy to set-
up 2
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 2.
[3] Copy to set-
up 3
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 3.
[4] Copy to set-
up 4
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 4.
[9] Copy to all Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
3.2.7 0-6* Password
0-60 Main Menu Password
Range: Function:
100 * [0 - 999 ] Define the password for access to the Main
Menu via the [Main Menu] key. If 0-61 Access
to Main Menu w/o Password is set to [0] Full
access, this parameter will be ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0] * Full access
Disables password defined in 0-60 Main
Menu Password.
[1] LCP: Read only Prevent unauthorized editing of Main Menu
parameters.
[2] LCP: No access Prevent unauthorized viewing and editing
of Main Menu parameters.
[3] Bus: Read only Read-only functions for parameters on
Fieldbus and/or FC standard bus.
[4] Bus: No access No access to parameters is allowed via
Fieldbus and/or FC standard bus.
[5] All: Read only Read-only function for parameters on LCP,
Fieldbus or FC standard bus.
[6] All: No access No access from LCP, Fieldbus or FC
standard bus is allowed.
If Full access [0] is selected then 0-60 Main Menu Password,
0-65 Personal Menu Password and 0-66 Access to Personal
Menu w/o Password will be ignored.
NOTE
A more complex Password protection is available for OEMs
upon request.
0-65 Quick Menu Password
Range: Function:
200 * [-9999 -
9999 ]
Define the password for access to the Quick
Menu via the [Quick Menu] key. If
0-66 Access to Quick Menu w/o Password is
set to [0] Full access, this parameter will be
ignored.
0-66 Access to Quick Menu w/o Password
Option: Function:
[0] * Full access
Disables the password defined in
0-65 Quick Menu Password.
[1] LCP: Read only Prevents unauthorised editing of Quick
Menu parameters.
[3] Bus: Read only Read only functions for Quick Menu
parameters on Fieldbus and/ or FC
standard bus.
[5] All: Read only read only function for Quick Menu
parameters on LCP, Fieldbus or FC standard
bus.
If
0-61 Access to Main Menu w/o Password is set to [0] Full
access then this parameter will be ignored.
0-67 Bus Password Access
Range: Function:
0 * [0 - 9999 ] Writing to this parameter enables users to
unlock the frequency converter from bus/MCT
10 Set-up Software.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 33
3
3