9. In the Configuration Approval dialog box, verify the safety configuration and click Approve to start writing the safety parameters.
e30be075.11
To abort the customization process and revert to the previous safety option state, click Cancel. The MCT 10 opens the Writing
Safety Parameters dialog box.
e30be076.11
10. When the progress bar reaches 100%, the safety parameters are written.
Commissioning
Installation Guide | VLT®Safety Option MCB 152
AN327351953089en-000101 / 130R0578| 31