Loading...
Enclosure FC 300 Power Recommended
fuse size
Recommended
Max. fuse
Recommended circuit
breaker
Max. trip level
Size [kW] Moeller [A]
B2 11
15
18
22
gG-25 (11)
gG-32 (15)
gG-32 (18)
gG-40 (22)
gG-63 - -
C2 30
37
45
55
75
gG-63 (30)
gG-63 (37)
gG-80 (45)
gG-100 (55)
gG-125 (75)
gG-80 (30)
gG-100 (37)
gG-125 (45)
gG-160 (55–75)
- -
D 37–315
gG-125 (37)
gG-160 (45)
gG-200 (55–75)
aR-250 (90)
aR-315 (110)
aR-350 (132–160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
gG-125 (37)
gG-160 (45)
gG-200 (55–75)
aR-250 (90)
aR-315 (110)
aR-350 (132–160)
aR-400 (200)
aR-500 (250)
aR-550 (315)
- -
E 355–560
aR-700 (355–400)
aR-900 (500–560)
aR-700 (355–400)
aR-900 (500–560)
- -
F 630–1200
aR-1600 (630–900)
aR-2000 (1000)
aR-2500 (1200)
aR-1600 (630–900)
aR-2000 (1000)
aR-2500 (1200)
- -
Table 10.4 525–690V, Frame Sizes B, C, D, E, and F