Table 159: Power Losses for Sine-wave Filter Option, 525–690 V
Model
525–550 V [W]
551–690 V [W]
NO
HO
NO
HO
N90K
1210
823
1106
752
N110
735
526
673
481
N132
1131
735
1032
673
N160
2063
1302
1888
1188
N200
1285
896
1177
820
N250
1814
1285
1657
1177
N315
2446
1814
2240
1657
N355
3560
2515
3264
2327
N400
4408
2966
4029
2709
N500
2487
1913
2274
1750
N560
2778
2486
2778
2274
N630
4075
3040
3730
2778
N710
5532
4075
5058
3730