EasyManua.ls Logo

Danfoss VLT Flow Drive FC 111 - Page 110

Danfoss VLT Flow Drive FC 111
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[87]
User define 7
[88]
User define 8
[100]
[1605] Main actual value [N2]
4.9.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus merging.
8-50 Coasting Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Table 196: Option:
[0]
Digital input
Activate coast via a digital input.
[1]
Bus
Activate coast via the serial communication port.
[2]
Logic AND
Activate coast via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate coast via the serial communication port or via 1 of the digital inputs.
8-51 Quick Stop Select
Default value: [3] Logic OR
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Table 197: Option:
[0]
Digital input
Activate quick stop via a digital input.
[1]
Bus
Activate quick stop via the serial communication port.
[2]
Logic AND
Activate quick stop via the fieldbus/serial communication port, and via 1 of the digital inputs.
[3]
Logic OR
Activate quick stop via the serial communication port or via 1 of the digital inputs.
8-52 DC Brake Select
Default value: -
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the DC brake function via the terminals (digital input) and/or via the bus.
AU363928304090en-000101 / 130R0982110 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Related product manuals