[1605] Main actual value [N2]
4.9.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus merging.
8-50 Coasting Select
Default value: [3] Logic OR
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Table 196: Option:
Activate coast via a digital input.
Activate coast via the serial communication port.
Activate coast via the fieldbus/serial communication port, and via 1 of the digital inputs.
Activate coast via the serial communication port or via 1 of the digital inputs.
8-51 Quick Stop Select
Default value: [3] Logic OR
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the quick stop function via the terminals (digital input) and/or via the bus.
Table 197: Option:
Activate quick stop via a digital input.
Activate quick stop via the serial communication port.
Activate quick stop via the fieldbus/serial communication port, and via 1 of the digital inputs.
Activate quick stop via the serial communication port or via 1 of the digital inputs.
8-52 DC Brake Select
Change during operation: True
N O T I C E
This parameter is active only when parameter 8-01 Control Site is set to [0] Digital and control word.
Select control of the DC brake function via the terminals (digital input) and/or via the bus.