Table 34: Range:
0-61 Access to Main Menu w/o Password
Default value: [0] Full access
Change during operation: True
Table 35: Option:
Disable the password defined in parameter 0-60 Main Menu Password.
Prevent unauthorized editing of Main Menu parameters.
Prevent unauthorized viewing and editing of Main Menu parameters.
Provide read-only access to parameters via fieldbus.
Prevent unauthorized editing of main menu parameters and provides read-only access to parameters via
fieldbus.
4.3 Parameter Group 1-** Load and Motor
Parameters related to the motor nameplate load compensations and application load type.
4.3.1 1-0* General Settings
Define whether the drive operates in speed mode or torque mode; and whether the internal PID control should be active or not.
1-00 Configuration Mode
Default value: [0] Open Loop
Change during operation: True
Select the application control principle to be used.
Table 36: Option:
Motor speed is determined by applying a speed reference or by setting the wanted speed when in hand-on
mode. Open loop is also used if the drive is part of a closed-loop control system based on an external PI con-
troller providing a speed reference signal as output.
N O T I C E
When set for closed loop, the commands Reversing and Start Reversing do not reverse the direction of the
motor.
A reference from the built-in PI controller determines the motor speed. The built-in PI controller varies the mo-
tor speed as of a closed-loop control process (for example, constant pressure or flow). Configure the PI control-
ler in parameter group 20-** Drive Closed Loop.
1-01 Motor Control Principle
Change during operation: False
Select U/f mode or VVC
+
mode as motor control principle.
AU363928304090en-000101 / 130R098240 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide