Table 34: Range:
Min: 0
Max: 999
Default value: 0
0-61 Access to Main Menu w/o Password
Default value: [0] Full access
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Table 35: Option:
[0]
Full access
Disable the password defined in parameter 0-60 Main Menu Password.
[1]
LCP: Read only
Prevent unauthorized editing of Main Menu parameters.
[2]
LCP: No access
Prevent unauthorized viewing and editing of Main Menu parameters.
[3]
Bus: Read only
Provide read-only access to parameters via fieldbus.
[5]
All: Read only
Prevent unauthorized editing of main menu parameters and provides read-only access to parameters via
fieldbus.
4.3 Parameter Group 1-** Load and Motor
Parameters related to the motor nameplate load compensations and application load type.
4.3.1 1-0* General Settings
Define whether the drive operates in speed mode or torque mode; and whether the internal PID control should be active or not.
1-00 Configuration Mode
Default value: [0] Open Loop
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Select the application control principle to be used.
Table 36: Option:
[0]
Open
Loop
Motor speed is determined by applying a speed reference or by setting the wanted speed when in hand-on
mode. Open loop is also used if the drive is part of a closed-loop control system based on an external PI con-
troller providing a speed reference signal as output.
[3]
Process
Closed
Loop
N O T I C E
When set for closed loop, the commands Reversing and Start Reversing do not reverse the direction of the
motor.
A reference from the built-in PI controller determines the motor speed. The built-in PI controller varies the mo-
tor speed as of a closed-loop control process (for example, constant pressure or flow). Configure the PI control-
ler in parameter group 20-** Drive Closed Loop.
1-01 Motor Control Principle
Default value: [1] VVC
+
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: False
Select U/f mode or VVC
+
mode as motor control principle.
AU363928304090en-000101 / 130R098240 | Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals