13-03 Reset SLC
Default value: [0] Do not reset SLC
Change during operation: True
Table 221: Option:
Retain programmed settings in parameter group 13-** Smart Logic.
Reset all parameters in parameter group 13-** Smart Logic to default settings.
4.10.2 13-1* Comparators
Comparators are used for comparing continuous variables (such as output frequency, output current, and analog input) to fixed
preset values.
Par. 13-11
Comparator Operator
=
TRUE longer than.
. . .
. . .
Par. 13-10
Comparator Operand
Par. 13-12
Comparator Value
e30bb672.10
Illustration 16: Comparators
In addition, there are digital values that are compared to fixed time values. See the explanation in parameter 13-10 Comparator Oper-
and. Comparators are evaluated once in each scan interval. Use the result (True or False) directly. All parameters in this parameter
group are array parameters with index 0–5. Select index 0 to program comparator 0, select index 1 to program comparator 1, and so
on.
13-10 Comparator Operand
Default value: [0] Disabled
Change during operation: True
Select the variable to be monitored by the comparator.
Table 222: Option:
AU363928304090en-000101 / 130R0982 | 119Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide