Par. 13-43
Logic Rule Operator 2
Par. 13-41
Logic Rule Operator 1
Par. 13-40
Logic Rule Boolean 1
Par. 13-42
Logic Rule Boolean 2
Par. 13-44
Logic Rule Boolean 3
e30bb673.10
Illustration 17: Logic Rules
Priority of calculation
The results of parameter 13-40 Logic Rule Boolean 1, parameter 13-41 Logic Rule Operator 1, and parameter 13-42 Logic Rule Boolean 2
are calculated first. The outcome (True/False) of this calculation is combined with the settings of parameter 13-43 Logic Rule Operator
2 and parameter 13-44 Logic Rule Boolean 3, yielding the final result (True/False) of the logic rule.
13-40 Logic Rule Boolean 1
Default value: [0] False
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Select the 1
st
boolean (True or False) input for the selected logic rule.
Table 226: Option:
[0]
False
Enter the fixed value of False in the logic rule.
[1]
True
Enter the fixed value True in the logic rule.
[2]
Running
See parameter 13-01 Start Event for further description.
[3]
In range
See parameter 13-01 Start Event for further description.
[4]
On reference
See parameter 13-01 Start Event for further description.
[7]
Out of current range
See parameter 13-01 Start Event for further description.
[8]
Below I low
See parameter 13-01 Start Event for further description.
[9]
Above I high
See parameter 13-01 Start Event for further description.
[16]
Thermal warning
See parameter 13-01 Start Event for further description.
[17]
Mains out of range
See parameter 13-01 Start Event for further description.
[18]
Reversing
See parameter 13-01 Start Event for further description.
[19]
Warning
See parameter 13-01 Start Event for further description.
[20]
Alarm (trip)
See parameter 13-01 Start Event for further description.
[21]
Alarm (trip lock)
See parameter 13-01 Start Event for further description.
[22]
Comparator 0
Use the result of comparator 0 in the logic rule.
[23]
Comparator 1
Use the result of comparator 1 in the logic rule.
[24]
Comparator 2
Use the result of comparator 2 in the logic rule.
[25]
Comparator 3
Use the result of comparator 3 in the logic rule.
[26]
Logic rule 0
Use the result of logic rule 0 in the logic rule.
[27]
Logic rule 1
Use the result of logic rule 1 in the logic rule.
AU363928304090en-000101 / 130R0982 | 121Danfoss A/S © 2021.07