22-01 Power Filter Time
Default value: 0.50 s
Parameter type: Range
2-setup: All setups
Conversion index: -2
Data type: u_int16
Change during operation: True
Set the time constant for the filtered power readout. A higher value gives a more steady readout but a slower system response to
changes.
Table 381: Range:
Min: 0.02 s
Max: 10 s
Default value: 0.50 s
22-02 Sleepmode CL Control Mode
Default value: [0] Normal
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
This parameter is for sleep mode running in process closed-loop mode. Use this parameter to configure whether to detect the feed-
back for sleep mode.
Table 382: Option:
[0]
Normal
The feedback is detected. Some parameters are checked.
[1]
Simplified
The feedback is not detected. Only sleep speed and time are checked.
22-04 Check Valve Monitor
Default value: [0] Disabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
When this function is enabled, the drive monitors the status of check valves in the system, once a damaged check valve is detected,
the drive trips warning 159, Check Valve Failure.
Table 383: Option:
[0]
Disabled
Disable the function.
[1]
Enabled
Enable the function.
4.16.2 22-2* No-Flow Detection
Parameters for setting up no-flow and dry pump detection.
The drive includes functions for detecting if the load conditions in the system allow the motor to be stopped:
Low power detection
One of these 2 signals must be active for a set time (parameter 22-24 No-Flow Delay) before selected action takes place. Possible
actions to select (parameter 22-23 No-Flow Function):
No action
Warning
Alarm
Sleep mode
AU363928304090en-000101 / 130R0982 | 165Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide

Table of Contents

Other manuals for Danfoss VLT Flow Drive FC 111

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT Flow Drive FC 111 and is the answer not in the manual?

Danfoss VLT Flow Drive FC 111 Specifications

General IconGeneral
BrandDanfoss
ModelVLT Flow Drive FC 111
CategoryDC Drives
LanguageEnglish

Related product manuals