Table 453: Option:
25-51 Alternation Event
Default value: [0] External
Change during operation: True
Choose the event that will change the lead pump.
Table 454: Option:
Alternation time interval
25-52 Alternation Time Interval
Change during operation: True
Set the time period between automatic alternation of the lead pump.
Table 455: Range:
25-53 Alternation Timer Value
Change during operation: True
View the actual value of the alternation time interval timer.
Table 456: Range:
25-55 Alternate if Load <= 50%
Default value: [1] Enabled
Change during operation: True
Choose enable to change the variable-speed pump only if the pump load is less than 50%.
Table 457: Option: