Table 15: Option:
Resumes operation of the drive, maintaining the same local reference and the same start/stop condition (ap-
plied by [Hand On]/[Off] on the LCP or local start via a digital input) as before the drive was powered down.
Uses saved reference [1] to stop the drive, but at the same time retains the local speed reference in memory
before powering down. After mains voltage is reconnected, and after receiving a start command (pressing
[Hand On] key or using the local start command via a digital input), the drive restarts and operates at the re-
tained speed reference.
0-06 GridType
Default value: [Configuration dependent]
Change during operation: False
Select the grid type of the supply voltage/frequency.
N O T I C E
Not all options are supported in all power sizes.
IT Grid is a supply mains, where there are no connections to ground.
Delta is a supply mains where the secondary part of the transformer is delta connected and 1 phase is connected to ground.
Table 16: Option:
0-07 Auto DC Braking
Change during operation: False
Protective function against over voltage at coast in IT grid environment. This parameter is active only when [1] On is selected in this
parameter, and IT-grid options are selected in parameter 0-06 GridType.
Table 17: Option:
This function is not active.
AU363928304090en-000101 / 130R0982 | 33Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide