Par 1-55 [x]
Output Frequency
Par 1-56 [x]
1-55[3]
1-55[2]
1-55[1]
1-55[0]
1-56
[0]
1-56
[1]
1-56
[2]
1-56
[3]
1-56
[4]
1-56
[5]
e30ba166.11
Illustration 8: U/f Characteristic
Table 72: Range:
Default value: Configuration dependent
4.3.7 1-6* Load Depen. Setting
Parameters for adjusting the load-dependent motor settings.
1-62 Slip Compensation
Change during operation: True
Enter the % value for slip compensation to compensate for tolerances in the value of n
M,N
. Slip compensation is calculated automat-
ically, which is based on the nominal motor speed n
M,N
.
Table 73: Range:
1-63 Slip Compensation Time Constant
Change during operation: True
Enter the slip compensation reaction speed. A high value results in slow reaction, and a low value results in quick reaction. If low-
frequency resonance problems arise, use a longer time setting.
Table 74: Range:
1-64 Resonance Dampening
Change during operation: True
Enter the resonance damping value. Set parameter 1-64 Resonance Dampening and parameter 1-65 Resonance Dampening Time Con-
stant to help eliminate high-frequency resonance problems. To reduce resonance oscillation, increase the value of parameter 1-64
Resonance Dampening.
Table 75: Range:
AU363928304090en-000101 / 130R0982 | 53Danfoss A/S © 2021.07
Parameters
VLT® Flow Drive FC 111
Programming Guide