EasyManua.ls Logo

Danfoss VLT HVAC Basic Drive FC 101

Danfoss VLT HVAC Basic Drive FC 101
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-24 Terminal 54 Low Ref./Feedb. Value
Range: Function:
parameter 6-21 Terminal 54 High Voltage/
parameter 6-22 Terminal 54 Low Current.
6-25 Terminal 54 High Ref./Feedb. Value
Range: Function:
Size
related*
[-4999 -
4999 ]
Enter the reference or feedback value
that corresponds to the voltage or
current set in parameter 6-21 Terminal
54 High Voltage/
parameter 6-23 Terminal 54 High
Current.
6-26 Terminal 54 Filter Time Constant
Range: Function:
0.01 s* [0.01 - 10
s]
Enter the time constant, which is a rst-
order digital low-pass lter time constant
for suppressing electrical noise in terminal
54. A high time constant value improves
dampening, but also increases the time
delay through the lter.
6-29 Terminal 54 mode
Option: Function:
Select if terminal 54 is used for current
input or voltage input.
[0] Current mode
[1] * Voltage mode
3.7.4 6-7* Analog/Digital Output 45
Parameters for conguring the scaling and limits for
analog/digital output terminal 45. Analog outputs are
current outputs: 0/4–20 mA. Resolution on analog output
is 12 bit. Analog output terminals can also be set up as
digital output.
6-70 Terminal 45 Mode
Option: Function:
Set terminal 45 to act as analog output or
as digital output.
[0] * 0-20 mA
[1] 4-20 mA
[2] Digital Output
6-71 Terminal 45 Analog Output
Option: Function:
Select the function of terminal 45 as an
analog current output. See also
parameter 6-70 Terminal 45 Mode.
[254] DC-link voltage
T2/S2, 200–400 V
T4, 400–800 V
6-71 Terminal 45 Analog Output
Option: Function:
T5, 400–1000 V
T6, 500–1000 V
[0] * No operation
[100] Output
frequency
0–100 Hz
[101] Reference Min
Ref.
–Max
Ref.
[102] Feedback Min
FB
–Max
FB
[103] Motor Current 0–I
max
[106] Power 0–P
nom
[139] Bus Control 0–100%
[254] DC Link Voltage 0–65535 V
6-72 Terminal 45 Digital Output
Option: Function:
Select the function of
terminal 45 as a digital
current output. See also
parameter 6-70 Terminal 45
Mode. See
parameter 5-40 Function
Relay for description of the
options.
[0] * No operation
[1] Control Ready
[2] Drive ready
[3] Drive ready/remote control
[4] Standby / no warning
[5] Drive running
[6] Running / no warning
[7] Run in range/no warning
[8] Run on ref/no warning
[9] Alarm
[10] Alarm or warning
[12] Out of current range
[13] Below current, low
[14] Above current, high
[16] Below speed, low
[17] Above speed, high
[19] Below feedback, low
[20] Above feedback, high
[21] Thermal warning
[22] Ready, no thermal warning
[23] Remote, ready, no thermal
warning
[24] Ready, Voltage OK
[25] Reverse
[26] Bus OK
[35] External Interlock
[36] Control word bit 11
[37] Control word bit 12
[41] Below reference, low
[42] Above ref, high
Parameters
VLT
®
HVAC Basic Drive FC 101
58 Danfoss A/S © 04/2018 All rights reserved. MG18B502
33

Table of Contents

Other manuals for Danfoss VLT HVAC Basic Drive FC 101

Related product manuals