relay. For example, relay 1 cuts in contactor K1,
which becomes the lead pump.
K1 blocks for K2 via the mechanical interlock,
preventing mains from being connected to the
output of the drive (via K1).
Auxiliary break contact on K1 prevents K3 from
cutting in.
Relay 2 controls contactor K4 for on/o control of
the xed speed pump.
At alternation, both relays de-energize and now
relay 2 is energized as the 1
st
relay.
Application Examples Design Guide
MG16C302 Danfoss A/S © 11/2017 All rights reserved. 215
12 12