Normal overload 110% for 1 minute
IP 21 B1 B1 B1 B2
IP 55 B1 B1 B1 B2
IP 66 B1 B1 B1 B2
Line supply 200-240 V AC
Adjustable frequency drive
Typical Shaft Output [kW]
P5K5
5.5
P7K5
7.5
P11K
11
P15K
15
Typical Shaft Output [HP] at 208 V 7.5 10 15 20
Output current
Continuous
(3 x 200-240 V) [A]
24.2 30.8 46.2 59.4
Intermittent
(3 x 200-240 V) [A]
26.6 33.9 50.8
65.3
Continuous
kVA (208 V AC) [kVA]
8.7 11.1 16.6 21.4
Max. cable size:
(line, motor, brake)
[mm
2
/AWG]
2)
10/7 35/2
Max. input current
Continuous
(3 x 200-240 V) [A]
22.0 28.0 42.0 54.0
Intermittent
(3 x 200-240 V) [A]
24.2 30.8 46.2
59.4
Max. pre-fuses
1)
[A]
63 63 63 80
Environment
Estimated power loss
at rated max. load [W]
4)
269 310 447 602
Weight enclosure IP 20 [kg]
Weight enclosure IP 21 [kg] 23 23 23 27
Weight enclosure IP 55 [kg] 23 23 23 27
Weight enclosure IP 66 [kg] 23 23 23 27
Efficiency
3)
0.96 0.96 0.96 0.96
8. Specifications VLT
®
HVAC Drive Instruction Manual
140
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark