130BA491
Illustration 1.1: This certificate also covers FC 102 and FC 202!
1.1.11. IT Line
IT Line
Do not connect 400 V adjustable frequency drives with RFI filters to line supplies
with a voltage between phase and ground of more than 440 V.
For IT lines and delta ground (grounded leg), line voltage may exceed 440 V be-
tween phase and ground.
Par. 14-50
RFI 1
can be used to disconnect the internal RFI capacitors from the RFI filter to ground.
If this is done, it will reduce the RFI performance to A2 level.