130BA491
Illustration 1.1: This certificate also covers FC 102 and FC 202!
1.1.11. IT Line
IT Line
Do not connect 400 V adjustable frequency drives with RFI filters to line supplies
with a voltage between phase and ground of more than 440 V.
For IT lines and delta ground (grounded leg), line voltage may exceed 440 V be-
tween phase and ground.
Par. 14-50
RFI 1
can be used to disconnect the internal RFI capacitors from the RFI filter to ground.
If this is done, it will reduce the RFI performance to A2 level.
1. Safety VLT
®
HVAC Drive Instruction Manual
8
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT HVAC Drive and is the answer not in the manual?

Danfoss VLT HVAC Drive Specifications

General IconGeneral
TypeVLT HVAC Drive
STO (Safe Torque Off)Yes
EnclosureIP20
Output Frequency0-500 Hz
Brake ChopperBuilt-in (depending on frame size)
EMC FilterBuilt-in (depending on frame size)
CommunicationEthernet
Power Range0.37 kW to 630 kW
Input Voltage200-240V, 380-480V, 525-600V
Protection FeaturesOverload, Overvoltage, Undervoltage, Short Circuit, Ground Fault
Ambient Temperature-10°C to +50°C (with derating above +40°C)
Storage Temperature-25°C to +70°C
Relative Humidity5-95% (non-condensing)
Cooling MethodAir-cooled