Protection and Features:
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the adjustable frequency drive trips
if the temperature reaches 203°F ± 9°F [95 °C ± 5°C]. An overload temperature cannot
be reset until the temperature of the heatsink is below 158°C ± 9°C [70°C ± 5°C]
(Guideline - these temperatures may vary for different power sizes, enclosures, etc.).
VLT HVAC drive has an auto-derating function to prevent it's heatsink from reaching 203°
F [95°C].
The adjustable frequency drive is protected against short-circuits on motor terminals U,
V, W.
If a line phase is missing, the adjustable frequency drive trips or issues a warning (de-
pending on the load).
Monitoring of the intermediate circuit voltage ensures that the adjustable frequency drive
trips if the intermediate circuit voltage is too low or too high.
The adjustable frequency drive is protected against ground faults on motor terminals U,
V, W.
Line power supply (L1, L2, L3):
Supply voltage 200-240 V ±10%
Supply voltage 380-480 V ±10%
Supply voltage 525-600 V ±10%
Supply frequency 50/60 Hz
Max. imbalance temporary between line phases 3.0% of rated supply voltage
True Power Factor () 0.9 nominal at rated load
Displacement Power Factor (cos) near unity (> 0.98)
Switching on input supply L1, L2, L3 (power-ups) enclosure type A maximum twice/min.
Switching on input supply L1, L2, L3 (power-ups) enclosure type B, C maximum once/min.
Environment according to EN60664-1 overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering no more than 100,000 RMS sym-
metrical Amperes, 240/500/600 V maximum.
Motor output (U, V, W):
Output voltage 0 - 100% of supply voltage
Output frequency 0 - 1000 Hz
Switching on output Unlimited
Ramp times 1 - 3600 sec.
Torque characteristics:
Starting torque (Constant torque) maximum 110% for 1 min.
*
Starting torque maximum 120% up to 0.5 sec.
*
Overload torque (Constant torque) maximum 110% for 1 min.
*
*Percentage relates to the nominal torque for the VLT HVAC Drive.
8. Specifications VLT
®
HVAC Drive Instruction Manual
144
MG.11.A4.22 - VLT
®
is a registered Danfoss trademark
8