Digital output:
Programmable digital/pulse outputs 2
Terminal number 27, 29
1)
Voltage level at digital/frequency output 0 - 24 V
Max. output current (sink or source) 40 mA
Max. load at frequency output 1 k
Max. capacitive load at frequency output 10 nF
Minimum output frequency at frequency output 0 Hz
Maximum output frequency at frequency output 32 kHz
Accuracy of frequency output Max. error: 0.1% of full scale
Resolution of output frequency 12 bit
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Control card, 24 V DC output:
Terminal number 12, 13
Max. load : 200 mA
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same
potential as the analog and digital inputs and outputs.
Relay outputs:
Programmable relay outputs 2
Relay 01 Terminal number 1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
(Inductive load @ cos 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load) 60 V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load) 24 V DC, 0.1A
Relay 02 Terminal number 4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cos 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load) 80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load) 24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load) 240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cos 0.4) 240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load) 50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load) 24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO) 24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1 overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation
(PELV).