EasyManua.ls Logo

Danfoss VLT MCA 121 EtherNet/IP

Danfoss VLT MCA 121 EtherNet/IP
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Explanation of the Status Bits
Bit 00, Control ready:
Bit 00 = ‘0’ means that the frequency converter has tripped. Bit 00 = ‘1’
means that the frequency converter controls are ready, but that the pow-
er component is not necessarily receiving any power supply (in the event
of external 24 V supply to controls).
Bit 01, Drive ready:
Bit 01 = ‘1’. The frequency converter is ready for operation.
Bit 02, Coasting stop:
Bit 02 = ‘0’. The frequency converter has released the motor. Bit 02 =
‘1’. The frequency converter can start the motor when a start command
is given.
Bit 03, No error/Trip:
Bit 03 = ‘0’ means that the frequency converter is not in fault mode. Bit
03 = ‘1’ means that the frequency converter is tripped, and that a reset
signal is required to re-establish operation.
Bit 04, No error/Error (no trip):
Bit 04 = ‘0’ means that the frequency converter is not in fault mode. Bit
04 = ‘1’ means that there is a frequency converter error but no trip.
Bit 05, Reserved:
Bit 05 is not used in the status word.
Bit 06, No error / Trip lock:
Bit 06 = ‘0’ means that the frequency converter is not in fault mode. Bit
06 = ‘1’ means that the frequency converter is tripped, and locked.
Bit 07, No warning/Warning:
Bit 07 = ‘0’ means that there are no warnings. Bit 07 = ‘1’ means that a
warning has occurred.
Bit 08, Speedreference/Speed = reference:
Bit 08 = ‘0’ means that the motor is running, but that the present speed
is different from the preset speed reference. For example, this might oc-
cur while the speed is being ramped up/down during start/stop. Bit 08 =
‘1’ means that the present motor speed matches the preset speed refer-
ence.
Bit 09, Local operation/Bus control:
Bit 09 = ‘0’ means that [STOP/RESET] is activated on the control unit, or
that Local control in par. 3-13
Reference Site
is selected. It is not possible
to control the frequency converter via serial communication. Bit 09 = ‘1’
means that it is possible to control the frequency converter via the field-
bus/ serial communication.
Bit 10, Out of frequency limit:
Bit 10 = ‘0’, if the output frequency has reached the value in
par. 4-11
Motor Speed Low Limit [RPM]
or par. 4-13
Motor Speed High
Limit [RPM]
. Bit 10 = ‘1’ means that the output frequency is within the
defined limits.
Bit 11, No operation/In operation:
Bit 11 = ‘0’ means that the motor is not running. Bit 11 = ‘1’ means that
the frequency converter has a start signal or that the output frequency is
greater than 0 Hz.
Bit 12, Drive OK/Stopped, auto start:
Bit 12 = ‘0’ means that there is no temporary over temperature on the
inverter. Bit 12 = ‘1’ means that the inverter has stopped because of over
temperature, but that the unit has not tripped and will resume operation
once the over temperature stops.
Bit 13, Voltage OK/Voltage exceeded:
Bit 13 = ‘0’ means that there are no voltage warnings. Bit 13 = ‘1’ means
that the DC voltage in the frequency converter’s intermediate circuit is
too low or too high.
Bit 14, Torque OK/Torque limit exceeded:
Bit 14 = ‘0’ means that the motor current is lower than the torque limit
selected in par. 4-16 and 4-17 Torque limit. Bit 14 = ‘1’ means that the
torque limit in par. 4-16 and 4-17 Torque limit has been exceeded. The
nominal torque can be read in par. 16-16
Torque [Nm]
.
Bit 15, Thermal OK/limit exceeded:
Bit 15 = ‘0’ means that the timers for both motor thermal protection and
VLT thermal protection, have not exceeded 100%. Bit 15 = ‘1’ means that
one of the limits has exceeded 100%.
5.3 ODVA Control Profile
5.3.1 Control Word under Instances 20/70 and 21/71
Set par.8-10
Control Word Profile
to ODVA.
The control word in Instances 20 and 21 is defined as follows:
NB!
Bits 00 and 02 in Instance 20 are identical with bits 00
and 02 in the more extensive Instance 21.
Bit
Instance 20 Instance 21
Bit = 0 Bit =1 Bit = 0 Bit =1
00 Stop Run Fwd Stop Run Fwd
01 - - Stop Run Rev
02
No function Fault reset No function Fault reset
03 - - - -
04
----
05 - - - Net Ctrl
06
--- Net Ref
07-15 - - - -
MCA 121 EtherNet/IP 5 How to Control
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
27
5

Related product manuals