12-22 Process Data Config Read
Range: Function:
[[0 - 9] PCD read 0 - 9] Configuration of readable process data.
12-28 Store Data Values
Option: Function:
This parameter activates a function that stores all parameter values in the non-volatile memory
(EEPROM) thus retaining parameter values at power-down.
The parameter returns to “Off”.
[0] * Off The store function is inactive.
[1] Store All set-ups All parameter value will be stored in the non-volatile memory, in all four setups.
12-29 Store Always
Option: Function:
Activates function that will always store received parameter data in non-volatile memory (EEPROM).
[0] * Off
[1] On
6.2.4 EtherNet/IP
12-30 Warning Parameter
Range: Function:
[0000 – FFFF hex] Read only. Displays the EtherNet/IP specific 16-bit Status-word.
Bit
Description
0 Owned
1Not used
2 Configured
3Not used
4 Not used
5Not used
6 Not used
7Not used
8 Minor recoverable fault
9 Minor unrecoverable fault
10 Major recoverable fault
11 Major unrecoverable fault
12 Not used
13 Not used
14 Not used
15 Not used
12-31 Net Reference
Option: Function:
Read only. Displays the reference source in Instance 21/71.
[0] * Off Reference from the network is not active.
[1] On Reference from the network is active.
12-32 Net Control
Option: Function:
Read only. Displays the control source in Instance 21/71.
[0] * Off Control via the network is not active.
6 Parameters MCA 121 EtherNet/IP
38
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark