EasyManuals Logo

Danfoss VLT MCA 121 EtherNet/IP User Manual

Danfoss VLT MCA 121 EtherNet/IP
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #39 background imageLoading...
Page #39 background image
[1] On Control via the network is active
12-33 CIP Revision
Option: Function:
Read only. Displays the CIP-version of the option software.
[0] Major version (00 - 99)
[1] Minor version (00 - 99)
12-34 CIP Product Code
Range: Function:
1100 (FC
302) 1110
(FC 301)*
[0 – 9999] Read only. Displays the CIP product code.
12-37 COS Inhibit Timer
Range: Function:
[0 – 65.535 ms] Read only Change-Of-State inhibit timer. If the option is configured for COS operation, this inhibit
timer can be configured in the Forward Open telegram to prevent that continuously changing PCD
data generates extensive network traffic. The inhibit time is in milliseconds, 0 = disabled.
12-38 COS Filters
Range: Function:
[[0 - 9] Filter 0 – 9 (0000 -
FFFFhex)]
Change-Of-State PCD filters. Sets up a filter mask for each word of process data when operating in
COS-mode. Single bits in the PCD’s can be filtered in/out.
6.2.5 Other EtherNet Services
12-80 FTP Server
Option: Function:
[0] * Disable Disables the built-in FTP server.
[1] Enable Enables the built-in FTP server.
12-81 HTTP Server
Option: Function:
[0] * Disable Disables the build-in HTTP (web) server.
[1] Enable Enables the build-in HTTP (web) server.
12-82 SMTP Service
Option: Function:
[0] * Disable Disables the SMTP (e-mail) service on the option.
[1] Enable Enables the SMTP (e-mail) service on the option.
12-89 Transparent Socket Channel Port
Range: Function:
0* [0 – 9999] Configures the TCP port-number for the transparent socket channel. This enables FC-telegrams to
be sent transparently on Ethernet via TCP. Default value is 4000, 0 means disabled.
MCA 121 EtherNet/IP 6 Parameters
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
39
6

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT MCA 121 EtherNet/IP and is the answer not in the manual?

Danfoss VLT MCA 121 EtherNet/IP Specifications

General IconGeneral
BrandDanfoss
ModelVLT MCA 121 EtherNet/IP
CategoryControl Unit
LanguageEnglish

Related product manuals