EasyManua.ls Logo

Danfoss VLT MCA 121 EtherNet/IP - Status Word under Instances 20;70 and 21;71

Danfoss VLT MCA 121 EtherNet/IP
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Explanation of the Bits:
Bit 0, Run Fwd:
Bit 0 = "0" means that the VLT frequency converter has a stop command.
Bit 0 = "1" leads to a start command and the VLT frequency converter
will start to run the motor clockwise.
Bit 1, Run Rev:
Bit 1 = "0" leads to a stop of the motor. Bit 1 = "1" leads to a start of the
motor.
Bit 2, Fault Reset:
Bit 2 = "0" means that there is no trip reset. Bit 2 = "1" means that a trip
is reset.
Bit 3, No function:
Bit 3 has no function.
Bit 4, No function:
Bit 4 has no function.
Bit 5, Net Control:
Bit 5 = "0" means that the drive is controlled from the standard inputs.
Bit 5 = "1" means that EIP controls the drive.
NB!
Please note that changes will affect parameters 8-50
to 8-56.
Bit 6, Net Reference:
Bit 6 = "0" Reference is from the standard inputs. Bit 6 = "1" Reference
is from EIP.
NB!
Please note that changes will affect par. 3-15
Refer-
ence Resource 1
to par. 3-17
Reference Resource 3
.
For the Speed reference, see section
Bus speed refer-
ence value under Instances 20/70 and 21/71
.
5.3.2 Status Word under Instances 20/70 and 21/71
The status word in Instances 70 and 71 is defined as follows:
NB!
Bits 00 and 02 in Instance 70 are identical with bits 00
and 02 in the more extensive Instance 71.
Bit
Instance 70 Instance 71
Bit = 0 Bit =1 Bit = 0 Bit =1
00 No Fault Fault No Fault Fault
01 - - - Warning
02
- Running 1
Fwd
- Running 1 Fwd
03 - - - Running 2 Rev.
04
-- -Ready
05 - - - Ctrl from Net
06
-- -Ref. from Net
07 - - - At ref.
08-15
-- State Attribute
Explanation of the Bits:
Bit 0, Fault:
Bit 0 = "0" means that there is no fault in the frequency converter. Bit 0
= "1" means that there is a fault in the frequency converter.
Bit 1, Warning:
Bit 0 = "0" means that there is no unusual situation. Bit 0 = "1" means
that an abnormal condition has occurred.
Bit 2, Running 1:
Bit 2 = "0" means that the drive is not in one of these states or that Run
1 is not set. Bit 2 = "1" means that the drive state attribute is enabled or
stopping, or that Fault-Stop and bit 0 (Run 1) of the control word are set
at the same time.
Bit 3, Running 2:
Bit 3 = "0" means that the drive is in neither of these states or that Run
2 is not set. Bit 3 = "1" means that the drive state attribute is enabled or
stopping, or that fault-stop and bit 0 (Run 2) of the control word are set
at the same time.
Bit 4, Ready:
Bit 4 = "0" means that the state attribute is in another state. Bit 4 = "1"
means that the state attribute is ready, enabled or stopping.
Bit 5, Control from net:
Bit 5 = "0" means that the drive is controlled from the standard inputs.
Bit 5 = "1" means that EIP has control (start, stop, reverse) of the drive.
Bit 6, Ref from net:
Bit 6 = "0" means that the reference comes from inputs to the drive. Bit
6 = "1" means that the reference comes from EIP.
Bit 7, At reference:
Bit 7 = "0" means that the motor is running, but that the present speed
is different from the preset speed reference, i.e. the speed is being ram-
ped up/down during start/stop. Bit 7 = "1" means that the drive and
reference speeds are equal.
Bit 8 - 15, State attribute:
(Instance 71 only) Represents the state attribute of the drive, as indicated
in the following table:
5 How to Control MCA 121 EtherNet/IP
28
MG.90.J2.02 - VLT
®
is a registered Danfoss trademark
5

Related product manuals