8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the eldbus.
[0] Digital
input
Activates the set-up selection via a digital input.
[1] Bus Activates the set-up selection via the serial
communication port or eldbus option.
[2] Logic
AND
Activates the set-up selection via the eldbus/
serial communication port and via 1 of the
digital inputs.
[3] * Logic OR Activates the set-up selection via the eldbus/
serial communication port or via 1 of the digital
inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the preset reference selection
via the terminals (digital input) and/or via the
eldbus.
[0] Digital
input
Activates preset reference selection via a digital
input.
[1] Bus Activates preset reference selection via the
serial communication port or eldbus option.
[2] Logic AND Activates preset reference selection via the
eldbus/serial communication port and via 1 of
the digital inputs.
[3] * Logic OR Activates the preset reference selection via the
eldbus/serial communication port or via 1 of
the digital inputs.
8-57 Prodrive OFF2 Select
Select control of the frequency converter OFF2 selection via the
terminals (digital input) and/or via the eldbus. This parameter is
active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Prole is set to [1]
Prodrive prole.
Option: Function:
[0] Digital input
[1] Bus
[2] Logic AND
[3] * Logic OR
8-58 Prodrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the eldbus. This parameter is
active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Prole is set to [1]
Prodrive prole.
Option: Function:
[0] Digital input
[1] Bus
8-58 Prodrive OFF3 Select
Select control of the frequency converter OFF3 selection via the
terminals (digital input) and/or via the eldbus. This parameter is
active only when parameter 8-01 Control Site is set to [0] Digital
and ctrl. word, and parameter 8-10 Control Word Prole is set to [1]
Prodrive prole.
Option: Function:
[2] Logic AND
[3] * Logic OR
8-79 Protocol Firmware version
Range: Function:
Size related* [0 - 65535 ] Firmware revision: FC is in index 0;
Modbus is in index 1; indexes 2–4
are reserved.
8-80 Bus Message Count
Range: Function:
0* [0 - 65536 ] This parameter shows the number of valid
telegrams detected on the bus.
8-81 Bus Error Count
Range: Function:
0* [0 - 65536 ] This parameter shows the number of telegrams
with faults (for example CRC faults) detected
on the bus.
8-82 Slave Messages Rcvd
Range: Function:
0* [0 - 65536 ] This parameter shows the number of valid
telegrams sent by the frequency converter to
the slave.
8-83 Slave Error Count
Range: Function:
0* [0 - 65536 ] This parameter shows the number of error
telegrams, which could not be executed by the
frequency converter.
8-84 Slave Messages Sent
Range: Function:
0* [0 - 65536 ] This parameter shows the number of messages
sent from the slave.
8-85 Slave Timeout Errors
Range: Function:
0* [0 - 65536 ] This parameter shows the number of slave
timeout errors.
8-88 Reset FC port Diagnostics
Option: Function:
[0] * Do not reset
[1] Reset counter