Data Aire gForce DX - Recommended Line Sizing, Air Cooled Units; Hot Gas Lines

Data Aire gForce DX
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
Recommended Line Sizing, Air Cooled Units
Hot Gas Lines
Hot Gas Lines (Dual Circuit Systems)
50 Equivalent Feet (15.2) Meters
Unit kW
Horizontal & Vertical Down
Vertical Up
21(6)
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
28(8)
7/8” (22 mm) O.D.
5/8” (16 mm) O.D.
35(10)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
46(13)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
56(16)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
70(20)
1-1/8" (29 mm) O.D.
7/8” (22 mm) O.D.
91(26)
1-1/8" (29 mm) O.D.
1-1/8" (29 mm) O.D.
106(30)
1-1/8" (29 mm) O.D.
1-1/8" (29 mm) O.D.
100 Equivalent Feet (30.5) Meters
21(6)
5/8” (16 mm) O.D.
5/8” (16 mm) O.D.
28(8)
7/8” (22 mm) O.D.
5/8” (16 mm) O.D.
35(10)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
46(13)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
56(16)
1-1/8" (29 mm) O.D.
7/8” (22 mm) O.D.
70(20)
1-1/8" (29 mm) O.D.
7/8” (22 mm) O.D.
91(26)
1-1/8" (29 mm) O.D.
1-1/8" (29 mm) O.D.
106(30)
1-1/8" (29 mm) O.D.
1-1/8" (29 mm) O.D.
150 Equivalent Feet (45.7) Meters
21(6)
7/8” (22 mm) O.D.
5/8” (16 mm) O.D.
28(8)
7/8” (22 mm) O.D.
5/8” (16 mm) O.D.
35(10)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
46(13)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
56(16)
1-1/8" (29 mm) O.D.
7/8” (22 mm) O.D.
70(20)
1-1/8" (29 mm) O.D.
7/8” (22 mm) O.D.
91(26)
1-3/8" (35 mm) O.D.
1-1/8" (29 mm) O.D.
106(30)
1-3/8" (35 mm) O.D.
1-1/8" (29 mm) O.D.
200 Equivalent Feet (61.0) Meters
21(6)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
28(8)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
35(10)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
46(13)
7/8” (22 mm) O.D.
7/8” (22 mm) O.D.
56(16)
1-1/8" (29 mm) O.D.
1-1/8" (29 mm) O.D.
70(20)
1-3/8" (35 mm) O.D.
1-3/8" (35 mm) O.D.
91(26)
1-3/8" (35 mm) O.D.
1-3/8" (35 mm) O.D.
106(30)
1-3/8" (35 mm) O.D.
1-1/8" (29 mm) O.D.