EasyManua.ls Logo

Data Aire gForce DX - Water;Glycol-Cooled System Charging

Data Aire gForce DX
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
60
Table 5 Discharge Head Pressure
Refrigerant
Head Pressure
R-410A
380 PSIG (2620 kPa) or higher
R-407C
230 PSIG (1586 kPa) or higher
While charging during the summer, meter refrigerant through the suction line until the level of
liquid in the receiver sight glass is approximately 1/3 from the bottom (the level ball in the
receiver will start to float) of the sight glass. A liquid charging adapter should be used to
prevent liquid refrigerant from entering the compressor. Charge each circuit to the value
shown in the
Table 7 Packaged Units with Receivers
below.
See 5.7.3
Charging the Fixed Speed
Compressor for charging the fixed speed compressor
except use the table below for the proper charge conditions.
Water/Glycol-Cooled System Charging
All water/glycol cooled units are factory charged with refrigerant. The superheat at the
compressor suction line at least 6 inches (152 mm) away from the compressor. The water
regulating valve should be adjusted to maintain the required conditions. Field charging, if
required, of water/glycol systems should be done by referring to the unit’s electrical
nameplate. The factory charge is indicated on the nameplate. Although this figure represents
the initial factory charge, it is still necessary to measure and note proper unit operation
including superheat, head and suction pressure. Some adjustment of charge may be required.
Adjust the refrigerant charge until the sight glass has sparse bubbles. The system should be
allowed to stabilize for 15 to 20 minutes before meaningful measurements can be taken. After
the system stabilize, verification of a few key measurements should be noted.
Table 6 Packaged Units without Receivers
Acceptable parameters range for water/glycol packaged units without receiver, with return air
temperature of 65°F to 85°F and entering water/glycol temp of 65 - 85°F
Refrigerant
Liquid Line
Pressure PSIG (kPa)
Liquid Line
Temp °F (°C)
Suction Pressure
PSIG (kPa)
Suction Sat.
Temp °F (°C)
Subcooling
Temp °F (°C)
Superheat
Temp °F (°C)
R410A
290 to 390
(1999 to 2689)
85 to 100
(29.4 to 37.8)
103 to 130
(710 to 896)
or greater
33 to 45
(0.56 to 7.2)
8 to 15
(-13.3 to -9.4)
12 to 18
(-11.1 to -7.8)
R407C
245 to 285
(1689 to 1965)
106 to 115
(41.1 to 46.1°)
53 to 70
(365 - 483)
or greater
33 to 45
(0.56 to 7.2)
8 to 10°
(-13.3 to 12.2°)
8 to 15°
(-13.3 to -9.4°)

Table of Contents

Related product manuals