28
Field Piping, Remote Condenser Below Evaporator
Figure 8 Typical Remote Condenser Below Evaporator
NOTES: Unless otherwise specified by job specific documentation
1. This is recommended piping. All piping to be per local and/or state codes.
2. Condenser to be no more than 15 feet (4.6 m) below evaporator.
3. Slope horizontal lines downward in the direction of the refrigerant flow, ½” for every 10
feet (3 m) of line length.
4. Inverted trap needed on suction line when compressor is outdoors only.