Water Sensing Cable (Optional)
Some units may be equipped with an optional water detection cable in addition to or in lieu of
the condensate probe. The cable can sense moisture anywhere along its length. It is typically
placed below the unit in a rectangular pattern that matches the perimeter of the unit. The cable
is connected to the terminal board and ready for installation. Cable lengths will vary depending
on the original order and specifications. Care should be taken when installing the cable. Be
sure the cable is not touching metal and/or any debris under the raised floor.
Remote Temperature and Humidity Sensors (Optional)
Although existing unit mounted sensors can be removed for remote mounting, the remote
sensor option provides a more convenient means of field installation. This is because the
sensors are already connected to a predetermined length of cable and come mounted in a
remote sensor enclosure. The temperature and humidity sensors require a total of five wires
and should be twisted, shielded cable type.
When ordered, the remote sensors are shipped with 35 feet (11 m) standard length or 50 feet
(15 m) to 100 feet (30.5 m) optional length of cable and comes mounted in a decorative wall
mounted enclosure.
Manual Override Switch Board
For testing and during start-up each gForce unit is provided with manual override slide
switches. There are seven (7) slide switches. One for each of the following functions:
Figure 12 Manual Override Switch Board