Condensate Pumps (Optional)
If a gravity drain is not available, a condensate pump is an optional item. Condensate pumps
may be unit mounted or ship loose for field assembly and wiring. Factory mounted pumps are
pre-wired. While no outside power source is required, field piping is still a requirement. If the
condensate pumps are shipped loose, a separate source of power is normally required.
Condensate pumps are available in various voltages, therefore, always check the pump power
requirements before connecting power.
WARNING: For shipped loose and field installed condensate pumps, a
separate power source must be supplied to avoid any flooding problems.
Wire the pump to shut the system off in case of overflow or pump failure.
WARNING: The condensate drain MUST be connected to an external
drain line (provided by others) before unit start up. Without field piping
condensate water will damage internal components.
Condensate pumps which ship loose, normally require a separate source of power. Always
check the pump power requirements before connecting power. Condensate pumps are
available in various voltages.
Factory installed condensate pumps are wired to display a “HIGH CONDENSATE WATER
LEVEL” alarm. The wiring for this must be done in the field on pumps that ship loose.
Condensate Probe
One (1) condensate probe for sensing water under the floor is standard and is included with
this unit. This comes in a plastic bag with about 15 feet (4.6 m) of coiled-up wire. The
condensate probe is a rectangular box that is typically placed below the unit in a location
where the water is likely to accumulate. Additional probes are available as an option.
Place the probe flat on the floor on top of a thin layer of non-conductive silicone. Secure the
attached wires where necessary. A longer length of standard hookup wire may be used if
required.
WARNING: Failure to remove the condensate probe from the plastic bag
and uncoil the length of wire attached to the probe will leave the unit
unprotected for sensing water under the unit and can result in a nuisance
water detected alarm. Remove/disconnect the probe if it is not to be
used.