EasyManua.ls Logo

Datakom D-300 MK2 - Page 86

Datakom D-300 MK2
139 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
D-300 MK2 User Manual Firmware V-6.3
L052D01-EN - 86 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
GCB Alarm Level
-
0
1
0
0: shutdown alarm
1: loaddump alarm
Genset MCB Fail Timer
sec
0
600
2.0
If a genset MCB feedback input is
defined and if the genset MCB fails to
change position before the expiration of
this timer, then a fault condition occurs.
Genset Phase Order
Check Enable
-
0
1
0
0: genset phase order checking
disabled
1: if genset phase order is faulty, then a
genset phase order fail loaddump alarm
is given.
Busbar Fail Timer
sec
0
30
2.0
When a genset closes to the Busbar, if
the mater genset controller does detect
the Busbar voltage at the expiration of
this period, a “BUSBAR FAIL” fault
condition will occur.
Busbar Ready Timer
sec
0
30
2.0
This is the delay after all generators
close to the busbar and before the
master genset controller acknowledges
“Busbar ready” signal.
Multi Load Subtract
Power Level
kW
0
65000
0
When the genset active power goes
over this limit, the controller will start
substracting load as described in
chapter Five Step Load Management.
Multi Load Add Power
Level
kW
0
65000
0
When the genset active power goes
below this limit, the controller will start
adding load as described in chapter
Five Step Load Management.
Multi Load Subtract Start
Delay
sec
0
36000
0
If the load stays over the Multi Load
Substract Power Level parameter
during this timer, then 1 step of load is
substracted.
Multi Load Subtract Wait
Delay
sec
0
36000
0
This is the minimum period between
two load subtract operations.
Multi Load Add Start
Delay
sec
0
36000
0
If the load stays below the Multi Load
Add Power Level parameter during this
timer, then 1 step of load is added.
Multi Load Add Wait
Delay
sec
0
36000
0
This is the minimum period between
two load add operations.
Excess power Warning
Limit
kW
0
50000
0
If the genset active power goes above
this limit then the controller will give an
Excess Power Warning.
16.2. ELECTRICAL PARAMETERS GROUP (continued)

Table of Contents

Related product manuals