Fire/Smoke Detectors Building Construction
Other than the controls of the DRY-O-TRON® unit, no electronic components or other equipment that is subject
to moisture damage should be installed in the DRY-O-TRON® unit, unless special arrangements are made with
Dectron at time of sale.
Where fire/smoke detectors must be located in any duct that may cool below room-air dewpoint (usually 60 to
70°F (15 to 21°C) for natatoriums), either the detector must be heated to prevent condensation, or must be located
well within the heated space of the building. No unheated electronics, including fire/smoke detectors, should be
located in ducts exposed to outdoor air, due to the risk of condensation.
Moist air from the building will move through ducts, even with the blower off. If air contacts any surface below its
dew point (usually 60 to 70°F (15 to 21°C) for natatoriums), water will condense onto that surface.
Should fire/smoke detectors be required
to be inside the DRY-O-TRON® unit, use care in locating any such
device to prevent interference with service access. Service access requires that all doors and panels be easily
operable and that all service spaces between pipes and other components remain open for entry and exit.
Dectron accepts no responsibility for delays, extra costs, or other damages due to misplacement of a fire/smoke
detector by others.
DECTRON
Sample
Appearance may vary.
Do not install unheated electronics inside
ducts that are exposed to outdoor air, or
that might go below room dewpoint tem-
perature for any other reason.
Do not install any devices that will interfere with
1. the opening of any unit access panels, or
2. the opening of any unit doors, or
3. service access to any internal parts.
NOTE: Spaces between internal components
may be required for access.
BUILDING
CONSTRUCTION
Risk of fire/smoke alarm failure. Can cause property damage, injury, or death.
Placement of fire/smoke detectors is critical for reliability. Read and follow the
instructions in this manual, the alarm manual, and all applicable codes.
WARNING
2.21

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DS 010 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DS 010 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DS 010
CategoryController
LanguageEnglish

Related product manuals