Startup Enable Operation
Dectron, Inc. March 2012
DECTRON
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
Data subject to change without notice.
228
IMPORTANT!
This energy recycling dehumidification system has been tested under design conditions at the factory.
Start-up must be performed by a qualified factory-trained service and installation technician.
Once startup is completed, all portions of the “Startup Report and Warranty Registration” form must
be completely filled in and a copy must be sent to the Dectron factory in order to register and validate
the warranty. A copy can be faxed to the factory office at 514-334-9184.
Risk of equipment damage.
Do NOT turn on the electric power unless the branch-circuit voltage matches that specified on the
unit nameplate.
Risk of equipment damage.
Indoor units require a minimum equipment-room temperature of 70°F (21°C). Units may not start
reliably at lower equipment-room temperatures. Contact Dectron if this temperature cannot be
maintained.
Risk of equipment damage.
Unless otherwise stated in the unit submittal data, the unit requires a minimum temperature of 78°F
(25.6°C) in the space it serves for proper operation of the refrigeration system(s). Before enabling a
compressor, allow the blower and space heater to raise the space temperature above 78°F (25.6°C).
Risk of equipment damage.
Where compressors are equipped with oil-level sight glasses, the oil level should be monitored
closely during the first 10 hours of operation.
IMPORTANT!
Heating, Cooling, or Dehumidifying Construction Sites
Risk of equipment damage. Risk of property damage.
The DRY-O-TRON
®
unit is not a convenience air conditioner. Its capacity is matched to the
expected load. Any damage to the unit and any performance reduction due to abuse or improper
installation will be obvious once the building begins normal use.
Never
use the unit to heat, cool, or dehumidify a construction site. The air coils must be protected
from construction dusts until all construction dusts have been removed from the space, from the
return duct, and from the outdoor-air intake (if any). Construction dusts bind to the cooling coil
permanently and cannot
be removed. Once bound, the dusts reduce heat transfer and airflow rate.
Filters will not prevent this.
The resulting performance reduction and possible component damage are not covered by the
Dectron warranty.
NOTICE
NOTICE
NOTICE
NOTICE
NOTICE
STARTUP
6.22

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DS 010 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DS 010 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DS 010
CategoryController
LanguageEnglish

Related product manuals