Name Description
Factory
value
Minimum Maximum Level
DP070
Domestic hot water temperature setpoint.
In the case of operation with a calorifier tank and pro
gramming via room unit corresponding to the comfort
setpoint [°C]
* Depends on the market
(55/60) * 35 (60/65) * User
DP150
Enabling the calorifier tank sensor/thermostat
0: DHW (Domestic Hot Water) sensor
1: DHW (Domestic Hot Water) thermostat
1 – – Installer
DP160
Temperature setpoint of the anti-legionella function
[°C]
65 60 90 Installer
DP200
DHW mode:
0: Domestic hot water programming (only available
with Room Unit)
1: Manual (boiler with calorifier tank) – Preheating ac
tive (instantaneous boiler) **
2: Antifreeze (boiler with calorifier tank) – No preheat
ing (instantaneous boiler)*
2 (*) / 1 (**) – – User
DP410
Duration of the DHW anti-legionella program [mi
nutes]
3 0 600 Installer
DP420 Maximum anti-legionella duration time [minutes] 15 0 360 Installer
DP430
Day to start the DHW anti-legionella program [day]
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
1 1 7 Installer
DP440
Starting time for the DHW anti-legionella program [mi
nutes]
30 0 143 Installer
GP007 Maximum fan speed in heating mode [rpm]
See chapter
"Service Set
tings"
– – Installer
GP008 Minimum fan speed [rpm]
See chapter
"Service Set
tings"
– – Installer
GP009 Fan starting speed [rpm]
4300
( 24/28 MI)
4800
( 30/35 MI)
2500 6000 Installer
GP082
Enabling domestic water circuit during chimney
sweep function
0 0 1 Installer
PP015
Pump post circulation run time after heating mode re
quest [min]
3 0 99 Installer
PP016 Maximum pump speed in heating mode [%] 100 85 100 Installer
PP018 Minimum pump speed in heating mode [%] 85 85 100 Installer
DEAIR Manual degassing function – – – Installer
CNF Configuration CN1 and CN2 - - - – – Installer
AD Searching for devices connected to the boiler PCB - - - – – Installer
Tab.116 Settings table with SMART TC°
Name Description
Factory
value
Minimum Maximum Level
CP060
Required ambient temperature (°C) in the zone in
the holiday/antifreeze period
6 5 20 User
CP070
Maximum ambient setpoint temperature (°C) in re
duced mode that enables switching to comfort
mode with climate control (with outside sensor)
17 5 30 User
en
9 Settings
190 INIDENS 7804841 - 02 - 20012022