Name Description
Factory
value
Minimum Maximum Level
CP080 Temperature (°C) set by SLEEP activity in the zone 17 5 30 User
CP081 Temperature (°C) set by HOME activity in the zone 20 5 30 User
CP082 Temperature (°C) set by AWAY activity in the zone 6 5 30 User
CP083
Temperature (°C) set by MORNING activity in the
zone
21 5 30 User
CP084
Temperature (°C) set by EVENING activity in the
zone
22 5 30 User
CP085
Temperature (°C) set by CUSTOM activity in the
zone
20 5 30 User
CP200
Required ambient temperature (°C) for the zone in
manual mode
20 5 30 User
CP220
Reduced mode heating curve offset (with outside
sensor).
30 15 90 Installer
CP240
Adjust the effect of the room unit compared to the
outside sensor
3 0 10 Installer
CP250 Correct the temperature measured by the room unit 0 -5 +5 User
CP320
Zone operating mode
0: Scheduling
1: Manual
2: Off
0 – – User
CP510 Temporary room setpoint per zone 20 5 30 User
CP550
Fireplace mode
0: Disabled
1: Enabled
0 – – User
CP570
Timer programme selected by User
0: Program 1
1: Program 2
2: Program 3
0 – – User
CP730
Boost when starting zone heating: Modify the heat
ing curve to speed up or slow down reaching of the
required comfort environment
0: Extremely slowly
1: More slowly
2: Slowly
3: Normal
4: Quickly
5: Extremely quickly
3 – – Installer
CP740
Building cooling speed when the heating is turned
off
0: Extremely slowly
1: Slowly
2: Normal
3: Quickly
4: Extremely quickly
2 – – Installer
CP750
Maximum preheating time [min] to reach the next
programmed comfort setpoint (with outside sensor
and programming via room unit)
0 0 240 Installer
DP060
Timer programme selected for DHW
0: Program 1
1: Program 2
2: Program 3
0 – – User
DP080
Reduced temperature setpoint for the domestic hot
water tank [°C]
35 10 60 User
DP337
Domestic hot water temperature setpoint for the
holiday period [°C]
10 10 60 User
9 Settings
en
7804841 - 02 - 20012022 INIDENS 191