Terminal Technical data Description
3-phase generator voltage input
33 Gen. voltage, L1 Generator voltage and frequency
34 Gen. neutral
35 Not used, must not be connec-
ted
36 Gen. voltage, L2
37 Not used, must not be connec-
ted
38 Gen. voltage, L3
3-phase generator current input
39 Gen. current L1, s1
Generator current
40 Gen. current L1, s2
41 Gen. current L2, s1
42 Gen. current L2, s2
43 Gen. current L3, s1
44 Gen. current L3, s2
Breaker relays
45 Relay output Generator circuit breaker/configurable, function NO (normal-
ly open)
Contact ratings 2 A 30 V DC/250 V AC
46 Relay output
47 Relay output Mains circuit breaker/configurable, function NC (normally
closed). With "Option M19" the relay is NO.
Contact ratings 2 A 30 V DC/250 V AC
48 Relay output
Modbus RS-485 interface
49 B (-)
Modbus RS-485 RTU or ASCII50 GND
51 A (+)
CAN bus port A: Engine interface
53 CAN-H
CAN J1939 engine communication54 Com
55 CAN-L
Optional CAN bus port B: AOP-2 interface
57 CAN-H
CAN communication line to AOP-258 Com
59 CAN-L
Optional CAN bus port B: External I/O interface
57 CAN-H
CAN communication port to external I/O
58 Com
59 CAN-L